+7 351 239-90-31

Switchgear and control gear – SCG

Series SCG 2-12Р up to 10 kV with lower drawout element
Switchgear and control gear – SCG

Request price on «SCG 2-12Р» or contact our manager a convenient way for you

Description

Switchgear and control gear (SCG) of Series SCG 2-12Р are designed for operation in 3-phase 50 Hz and 60 Hz, 6 kV and 10 kV rated AC voltage electric installations for a system with a neutral insulated or earthed via arc suppression coil, in moderate (N) climate, placement category 3 according to GOST 15150.

Switchgears (SG) used for electric power receipt and distribution are assembled from the SCG. Their operation principle is determined by an aggregate of circuitry of the main and auxiliary circuits.

Specifications

Parameter designation Parameter value
High-voltage (HV) side rated voltage, kV 6; 10
High-voltage (HV) side maximum operating voltage, kV 7,2; 12
Rated current of main circuits, A 630; 1000; 1600; 2000; 2500; 3150
Rated breaking current of the chamber SUM with vacuum circuit breaker, kA
20; 31,5
Peak withstand current of cells with vacuum circuit breaker, kA 32; 51, 64
Rated voltage of auxiliary circuits, V:
– AC and DC protection, control and alarm circuits
– voltage measuring transformers circuits
– lighting

220
100
36

 

Symbol structure

SCG Х - ХХХ - Х - Х / Х - Х ХХ

SCG is a switchgear and control gear manufactured by Chelyabinsk Electric Equipment Plant LLC

O – outdoor installation

Modification: 2-12P; HVDS; 2HVDC

Rated voltage, kV

Classification of lead-out on incoming line side:

  • C – cable;
  • O – overhead

Classification of lead-out on outgoing line side:

  • C – cable;
  • O – overhead

Rated current, A (630; 1000; 1600; 2000; 2500; 3150)

Climatic modification and placement category according to GOST15150-69

 

  • Come - we will pay

    Travel expenses, airfare, hotel at our expense

    The promotion is valid until December 1, 2016

  • Delivery at our expense

    When ordering the equipment in the amount of 5 mln. rub.

    The promotion is valid until December 1, 2016

  • Design classification

    SUM classification attributes Design
    Insulation level according to GOST 1516.3 Normal, level "b"
    Insulation type Air insulation
    Busbar insulation
    With non-insulated buses
    With insulated buses
    In term of presence of draw-out elements
    With draw-out elements;
    Without draw-out elements
    In terms of servicing conditions
    With bilateral maintenance;
    With unilateral maintenance
    In terms of arrangement of draw-out element
    Low;
    Middle
    In terms of installation method
    For indoor installation in electrical equipment rooms;
    For outdoor installation
    In terms of climatic modifications and placement category
    Placement category 3, climatic modification N
    according to GOST 15150, GOST 15543.1

     

    Structural design

    Structural design

    Main elements of SCG:

    • housing;
    • draw-out element;
    • earthing lead;
    • shutter mechanism;
    • arc flash protection devices;
    • circuits of relay protection and emergency control, feed-line consideration and telemechanics.

    SCG housing

    SCG housing

    SCG housing is a metal structure made of sheet rollformed sections. The housing components manufacturing process starts in the design engineering department, then the drawings are sent to the laser machine shop where future housing parts are being cut from sheet metal. Upon completion of the cutting process, fabricated materials are sent to the bending machine, and then welding and surface preparation for powder coating occur. Metal thickness of the housing parts varies from 1 to 5 mm.

    Provisions are made in the SCG housing design for separation of compartments into collecting buses compartment, vacuum circuit breaker compartment, cable connection compartment and RPA compartment.

    Reviews

    Выражаем благодарность коллективу ООО «ЧЗЭО» за оперативную поставку комплектных распределительных устройств для выполнения аварийно-восстановительных работ на участке пенопропитки с горизонтальными автоклавами филиал ООО «Донкарб Графит» территория «Челябинский завод электрооборудования» г.Челябинск. Поставленные на объект КРУ-2-12Р были изготовлены в обусловленные договором сроки.

    Read completely

    Photo

  • Come - we will pay

    Travel expenses, airfare, hotel at our expense

    The promotion is valid until December 1, 2016

  • Delivery at our expense

    When ordering the equipment in the amount of 5 mln. rub.

    The promotion is valid until December 1, 2016